How to set the braking parameters of a 45KW VFD?

Nov 11, 2025Leave a message

As a supplier of 45KW Variable Frequency Drives (VFDs), I often receive inquiries from customers about setting the braking parameters of these drives. Properly setting the braking parameters is crucial for the safe and efficient operation of the motor controlled by the VFD. In this blog post, I will guide you through the process of setting the braking parameters of a 45KW VFD, explaining the key concepts and providing practical tips.

Understanding the Basics of Braking in VFDs

Before diving into the parameter - setting process, it's important to understand the basic principles of braking in VFDs. When a motor is running, it stores kinetic energy. When the VFD reduces the frequency to slow down the motor, the motor acts as a generator, converting the kinetic energy back into electrical energy. This electrical energy needs to be dissipated properly to avoid over - voltage in the DC bus of the VFD.

There are two main types of braking methods in VFDs: dynamic braking and regenerative braking.

  • Dynamic Braking: In dynamic braking, the excess electrical energy is dissipated as heat in a braking resistor. The VFD monitors the DC bus voltage, and when the voltage exceeds a certain threshold, it activates a braking transistor to connect the braking resistor to the DC bus, allowing the energy to be dissipated.
  • Regenerative Braking: Regenerative braking returns the excess electrical energy back to the power supply. This method is more energy - efficient but is also more complex and expensive.

Factors Affecting Braking Parameter Settings

Several factors need to be considered when setting the braking parameters of a 45KW VFD:

  1. Motor Inertia: The inertia of the motor and the load it drives affects the amount of kinetic energy that needs to be dissipated during braking. Higher inertia systems require more braking power.
  2. Braking Torque Requirement: The required braking torque depends on the application. For example, applications that require rapid stops, such as conveyor belts in some industrial settings, need higher braking torque.
  3. DC Bus Voltage Threshold: This is the voltage level at which the VFD activates the braking circuit. Setting this threshold too low may cause the braking circuit to activate frequently, while setting it too high can lead to over - voltage protection tripping.
  4. Braking Resistor Selection: If using dynamic braking, the resistance value and power rating of the braking resistor are critical. A resistor with too high a resistance may not dissipate the energy fast enough, while a resistor with too low a resistance can cause excessive current and damage the braking transistor.

Step - by - Step Guide to Setting Braking Parameters

1. Determine the Braking Method

First, decide whether to use dynamic braking or regenerative braking based on your application requirements and budget. Dynamic braking is more commonly used for most general - purpose applications due to its simplicity and lower cost.

2. Calculate the Braking Energy

The braking energy (E) can be calculated using the formula (E=\frac{1}{2}J\omega^{2}), where (J) is the moment of inertia of the motor and load, and (\omega) is the angular velocity. The moment of inertia (J) can often be obtained from the motor and load manufacturer's specifications.

3. Select the Braking Resistor (for Dynamic Braking)

  • Resistance Value: The resistance value (R) of the braking resistor can be calculated using the formula (R = \frac{V_{DC}^{2}}{P_{braking}}), where (V_{DC}) is the DC bus voltage and (P_{braking}) is the required braking power.
  • Power Rating: The power rating of the braking resistor should be selected to handle the maximum braking power. It is recommended to choose a resistor with a power rating higher than the calculated value to account for short - term peak loads.

4. Set the DC Bus Voltage Threshold

In the VFD's parameter settings, find the parameter related to the DC bus voltage threshold for braking activation. A typical value for this threshold is around 10 - 15% higher than the normal DC bus voltage under full - load operation.

5. Set the Braking Time and Torque

  • Braking Time: Adjust the braking time parameter according to the application requirements. Shorter braking times require higher braking torque.
  • Braking Torque: Set the maximum braking torque parameter. This value should be within the capabilities of the motor and the VFD.

6. Test and Fine - Tune

After setting the initial parameters, conduct a test run. Monitor the DC bus voltage, motor speed, and braking performance. If the DC bus voltage exceeds the over - voltage protection limit, increase the resistance value of the braking resistor or adjust the DC bus voltage threshold. If the braking is too slow, increase the braking torque or reduce the braking time.

Frequency Controller For Ac MotorVariable Speed Drive For Single Phase Motor

Practical Tips

  • Consult the Manufacturer's Manual: The VFD manufacturer's manual provides detailed information about the braking parameter settings and recommended values for different applications.
  • Use Simulation Tools: Some VFD manufacturers offer simulation tools that can help you calculate the braking energy, select the appropriate braking resistor, and predict the braking performance.
  • Safety First: When working with braking resistors, be aware that they can get very hot during operation. Ensure proper ventilation and follow all safety regulations.

Related Products and Applications

If you are interested in other types of VFDs, we also offer Single Phase VFD To 3 Phase Motor, which allows you to power a three - phase motor from a single - phase power supply. Our Variable Speed Drive For Single Phase Motor provides precise speed control for single - phase motors, and the Frequency Controller for Ac Motor is suitable for a wide range of AC motor applications.

Conclusion

Setting the braking parameters of a 45KW VFD requires a good understanding of the basic principles of braking, consideration of various factors, and careful parameter adjustment. By following the steps and tips outlined in this blog post, you can ensure the safe and efficient operation of your VFD - controlled motor.

If you have any questions about setting the braking parameters of our 45KW VFDs or are interested in purchasing our products, please feel free to contact us for further discussion and negotiation. We are committed to providing high - quality VFDs and excellent technical support to meet your industrial needs.